删除或更新信息,请邮件至freekaoyan#163.com(#换成@)

光伏与燃气机热泵联合供能方案的研究

本站小编 Free考研考试/2022-01-16

宿向超, 杨昭
AuthorsHTML:宿向超, 杨昭
AuthorsListE:Su Xiangchao, Yang Zhao
AuthorsHTMLE:Su Xiangchao, Yang Zhao
Unit:天津大学机械工程学院,天津 300072
Unit_EngLish:School of Mechanical Engineering, Tianjin University, Tianjin 300072, China
Abstract_Chinese:为了节能减排, 同时保证系统的经济可行性, 提出了一种光伏和燃气机热泵联合供能的办公建筑供能方案, 对系统工作原理和季节性能进行了分析.以传统分供系统为参照对象, 提出了技术、环境和经济3方面的评价指标; 以某一典型办公建筑在4个不同地区的全年冷热电需求为基础, 设计了传统分供系统和光伏与燃气机热泵联合供能系统, 从技术、环境和经济角度, 分析和比较了两者的性能.结果表明:与传统供能系统相比, 新系统在4个典型地区的平均一次能源节约率达到34.6% , 在4个地区的CO2、SO2、R11和PM2.5的平均当量减排率分别为39.4% 、50.4% 、50.4% 和50.9% , 相对投资回报年限大约为4~5年.
Abstract_English:In order to save energy,reduce emission and ensure the economic feasibility of systems simultaneously,a photovoltaic power system-combined gas engine heat pump(GP)system for energy supply of office building scheme was presented in this paper. The working principle and seasonal performance of the system were analyzed. In comparison with a traditional separation production(SP)system,the technological,environmental and economical evaluation criteria were put forward. A typical office building in four different regions was selected as a case to design the SP system and GP system. The performance of both systems was analyzed and compared from the perspective of technology,environment and economy. The results show that compared with SP system,in four typical regions,the new system has an average primary energy saving ratio of 34.6%,and its CO2,SO2,R11 and PM2.5 equivalent emission reduction rates reach 39.4% ,50.4% ,50.4% and 50.9% ,respectively. Meanwhile,its relative payback period is about 4—5 years.
Keyword_Chinese:光伏; 燃气机热泵; 一次能源利用率; 污染物排放; 经济性
Keywords_English:photovoltaic; gas engine heat pump; primary energy ratio; pollutant emission; economy

PDF全文下载地址:http://xbzrb.tju.edu.cn/#/digest?ArticleID=5762
相关话题/方案 燃气