删除或更新信息,请邮件至freekaoyan#163.com(#换成@)

Strong self-flushing technique for heat exchanger of sewage source heat pump system

本站小编 哈尔滨工业大学/2019-10-23

Strong self-flushing technique for heat exchanger of sewage source heat pump system

XIAO Hong-xia1, SUN De-xing1, LI Xin2

1.chool of Municipal and Environmental Engineering, Harbin Institute of Technology, Harbin 150090, China;2.Architectural and Civil Engineering College, Shenyang University,Shenyang 110010, China



Abstract:

To better remove the contamination on the surface of a heat-exchanger in urban sewage source heat pump system (USSHPS), this paper analyzes the feasibility of strong self-flushing on the basis of experiments and presents a new on-line self-flushing technique, which alternately flushes part of heat transfer tubes. In addition, operation principles and the structure of the new heat-exchanger are introduced and the feasible economical and technological cleaning plans are given by design calculation and scheme comparison. The result shows that keeping each tube washed for one minute with 5 m/s, the operating cost is lower than $5 and when one flushing pump alternately flushes 10-20 heat exchangers, the saved costs of flushing 10 tubes alternately are over 4 times of the increased costs.

Key words:  sewage  heat pump  heat exchanger  alternation  self-flushing

DOI:10.11916/j.issn.1005-9113.2010.01.002

Clc Number:TU831.4

Fund:


相关话题/Strong self-flushing technique heat exchanger sewage